Comparative Assessment of Corona Behavior on Existing and Proposed 400‑kV Composite Insulator Assemblies

Authors

  • Noufal Asif Independent Researcher

Abstract

Composite long‑rod insulators installed on the 400‑kV overhead transmission lines at Section‑B Dubai Janub were found to exhibit corona discharge activity, indicated by dark surface spots and ultraviolet emissions concentrated near the energized end of the strings. Field inspections using visual, UV, and infrared scanning confirmed localized corona leakage on multiple circuits. To assess the issue, type tests—including corona extinction voltage, radio interference voltage (RIV), lightning impulse, and wet power frequency tests—were performed on new, cleaned, and in-service insulators. All samples complied with DEWA Standard 1.5.2.3.1.01‑Rev 3, and electric‑field simulations showed field intensities below corona‑critical thresholds. Despite successful laboratory and simulation results, field observations suggest that environmental pollution levels introduce conditions not fully replicated during testing, contributing to corona formation. A comparison of existing and proposed insulator assemblies revealed that current 400‑kV installations generally lack grading rings, whereas the proposed configurations incorporate them, potentially improving electric‑field distribution under polluted conditions. The investigation concludes that the observed black spots are directly associated with corona discharge and highlights the need to evaluate insulator design and hardware configuration for high‑pollution environments.

Downloads

Download data is not yet available.

Downloads

Published

2026-11-12

How to Cite

Asif, N. (2026). Comparative Assessment of Corona Behavior on Existing and Proposed 400‑kV Composite Insulator Assemblies. International Journal of Electrical Engineering and Applied Sciences (IJEEAS), 9(2). Retrieved from https://ijeeas.utem.edu.my/ijeeas/article/view/6421