Design and Hardware-In-the-Loop Validation of an IEC 61850-Based Coordinated Protection Scheme for Large-Scale Wind Farm Integration in Smart Grids

Authors

  • Yongama Gcelu Cape Peninsula University of Technology

Abstract

This paper presents the design, implementation, and validation of a coordinated protection scheme for high-voltage transformers integrated with a large-scale wind farm (LSWF) within a smart-grid environment. The proposed system is based on the IEC 61850 communication standard, employing Generic Object-Oriented Substation Event (GOOSE) messaging to achieve high-speed coordination among Intelligent Electronic Devices (IEDs). A modified IEEE 9-bus power system integrated with eighteen Vestas V117-4.2 MW wind turbine generator units (WTGUs) was modeled on the Real-Time Digital Simulator (RTDS) using RSCAD FX. The primary protection is implemented with the SEL-487E differential relay, while backup protection is provided by the SEL-751A feeder relay. Hardware-in-the-loop (HIL) validation using Omicron CMC 356 verified both the fault detection speed and the GOOSE communication latency under internal and external fault scenarios. Results show that the proposed IEC 61850-based protection scheme enhances fault detection accuracy, coordination reliability, and response speed compared to conventional methods.   

Downloads

Download data is not yet available.

Downloads

Published

2026-11-12

How to Cite

Gcelu, Y. (2026). Design and Hardware-In-the-Loop Validation of an IEC 61850-Based Coordinated Protection Scheme for Large-Scale Wind Farm Integration in Smart Grids. International Journal of Electrical Engineering and Applied Sciences (IJEEAS), 9(2). Retrieved from https://ijeeas.utem.edu.my/ijeeas/article/view/6393